Rinnai · Boiler troubleshooting

Testing a common vent when removing an existing boiler

I-Series Plus

What is going on

Removing a boiler from a shared vent can leave that vent oversized for the appliances still connected. Use this check on the remaining appliances (ANSI Z21.13 method). Follow the steps in order.

Likely causes

  • Common vent left oversized after the boiler is removed
  • Blockage, leakage, corrosion or poor pitch in the vent
  • Spillage at the draft hood of a remaining appliance

Check in this order

  1. Seal any unused openings in the common vent.
  2. Inspect the vent for correct size, horizontal pitch, blockage, restriction, leakage, corrosion and other defects that could make it unsafe.
  3. Close building doors and windows and doors to other spaces as far as practical. Run clothes dryers and any appliance not on the common vent. Run range hoods and bathroom exhaust fans at maximum speed. Do not run a summer exhaust fan. Close fireplace dampers.
  4. Start the appliance being checked, following its lighting instructions. Set the thermostat so it runs continuously.
  5. After five minutes of main burner operation, check for spillage at the draft hood relief opening with a lit match, candle or smoke.
  6. If each remaining appliance vents properly, return doors, windows, fans, dampers and other gas appliances to their normal condition.
  7. Correct any improper common vent operation so the installation meets the National Fuel Gas Code (ANSI Z223.1/NFPA 54) and/or CAN/CSA B149.1. When resizing the common vent, aim for the minimum size from the tables in Chapter 13 of the National Fuel Gas Code and/or CAN/CSA B149.1.

Applies to: Removing an existing boiler from a common vent with other gas appliances

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation manual, p. 144. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.