Weil-McLain · Boiler troubleshooting

Fill the system and set cold-fill pressure

SlimFit Series 2

What is going on

Fill only after the water meets the chemistry limits. Check the whole system for leaks.

Check in this order

  1. Close manual and automatic air vents and the boiler drain valve.
  2. Fill to the correct cold-fill pressure for the application.
  3. Keep operating pressure no higher than 80% of the relief valve setting for most systems.
  4. Check the full system for leaks during the initial fill and during startup testing. Repair every leak before going on.
  5. Refill to the correct pressure after air has been purged.

Applies to: SlimFit Series 2 startup

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual, p. 79. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.