Sizing the electric boiler

Vitotron 100 VLN2

What is going on

Size the boiler from a heat loss analysis. Do not oversize, since this adds cost to the boiler, wiring and materials.

Check in this order

  1. Run a heat loss analysis for the heated space.
  2. Convert the BTU/h load to kW by dividing by 3,413. Example: 33,513 BTU / 3,413 = 9.81 kW.
  3. Choose a boiler that slightly exceeds the kW requirement, by no more than 20%.
  4. For larger loads, cascade boilers in a parallel configuration as described in the piping section.
  5. If using propylene glycol, do not exceed a 50/50 glycol to water ratio. Glycol reduces heat transfer and efficiency.

Applies to: Vitotron 100 VLN2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotron 100 installation and service instructions, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.