Sizing the electric boiler
What is going on
Size the boiler from a heat loss analysis. Do not oversize, since this adds cost to the boiler, wiring and materials.
Check in this order
- Run a heat loss analysis for the heated space.
- Convert the BTU/h load to kW by dividing by 3,413. Example: 33,513 BTU / 3,413 = 9.81 kW.
- Choose a boiler that slightly exceeds the kW requirement, by no more than 20%.
- For larger loads, cascade boilers in a parallel configuration as described in the piping section.
- If using propylene glycol, do not exceed a 50/50 glycol to water ratio. Glycol reduces heat transfer and efficiency.
Applies to: Vitotron 100 VLN2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotron 100 installation and service instructions, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.