Weil-McLain · Boiler troubleshooting

Boiler water chemistry and system flushing

SlimFit Series 2

What is going on

The aluminum heat exchanger needs controlled water chemistry. Sediment and hard water scale can damage it.

Likely causes

  • Sediment build-up or corrosion in the heat exchanger
  • Hard water mineral scale
  • Oxygen carried in by make-up water
  • Continual fresh make-up water

Check in this order

  1. Keep system pH between 7.0 and 8.5 and check water chemistry.
  2. Add chemical treatment as required (see Startup — fill the system, p. 79).
  3. Flush the system thoroughly without the boiler connected; install a strainer if needed.
  4. Do not use petroleum-based cleaning or sealing compounds.
  5. Repair leaks at once and operate only as a closed-loop system.
  6. Do not add cold water to a hot boiler.

Applies to: All SlimFit Series 2 models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual, p. 5. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.