Viessmann · Boiler troubleshooting

Checking extension kit mixing valve rotation

Vitodens 200-W B2HA

What is going on

After power-on the boiler runs a self-test, opening and closing the mixing valve. If the flow temperature sensor reading drops when the valve should open, the motor direction is wrong or the valve set is fitted incorrectly.

Likely causes

  • Mixing valve motor turning in wrong direction
  • Mixing valve set incorrectly fitted

Check in this order

  1. Observe the self-test after switch-on.
  2. Set the mixing valve manually to Open and confirm the flow temperature sensor reads higher.
  3. To reverse motor direction remove the upper casing cover of the extension kit.
  4. At plug gS, switch the cores at terminals | and ~.
  5. Refit the casing cover.

Applies to: Vitodens 200-W B2HA 45, 60

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.