Viessmann · Boiler troubleshooting
Reset after auxiliary low gas pressure switch fault
What is going on
The burner stops and fault C1 is shown when gas pressure falls below the switch setting.
Likely causes
- Gas supply pressure is below the minimum operating pressure of 4.5 in. w.c.
Check in this order
- Press the low gas pressure switch reset button once.
- Reset the boiler control fault.
- If the fault returns, check the gas supply pressure.
- Contact the local gas company if the supply is below 4.5 in. w.c.
Applies to: Auxiliary low gas pressure switch
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.