Viessmann · Boiler troubleshooting

Check condensate drain and trap

Vitodens 200-W B2HA

What is going on

Keeps condensate draining freely to avoid a burner shutdown.

Likely causes

  • Condensate not draining freely, which builds up in the bottom of the boiler and causes a fault message

Check in this order

  1. Remove retaining clip A from condensate trap B.
  2. Disconnect flexible discharge tubing C from the trap.
  3. Remove the condensate trap from the boiler.
  4. Clean out debris and refill the trap with water.
  5. Reinstall the trap and secure it with the clip.
  6. Reconnect the flexible discharge tubing.
  7. Do not connect other drains, such as a water softener backwash pipe, to the condensate drain.

Applies to: Vitodens 200-W B2HA 19, 28, 35

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.