Viessmann · Boiler troubleshooting
Replace inlet damper linkage
What is going on
Linkage between the inlet damper bracket and the servomotor. Equipped on CM2 246 and 311 only.
Check in this order
- Remove the M4 (8 mm hex) nut that connects the linkage to the inlet damper bracket.
- Loosen the M5 (4 mm hex key) set screw that connects the linkage to the servomotor.
- Remove the linkage and fit the new one.
- Make sure the damper vents are fully open. Adjust the linkage if needed.
- Tighten to the torque in the torque table and reassemble in reverse order.
Applies to: CM2 246 and 311
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.