Access the control unit and external accessories box
What is going on
Opening the connection box and control unit to reach the terminals and main PCB.
Check in this order
- Remove both screws from the external accessories connection box front plate and set them aside.
- Loosen both retaining screws without removing them.
- Pull the box forward until the screws clear the guides.
- Swing the box down.
- Tilt the bottom of the box cover forward, lift it off the locating pins and set it aside.
- Slide both sides of the programming unit cover closed.
- Release the hinged hooks on both sides of the control unit.
- Lift the hinged cover, then fold the control unit down.
- Release the locking tabs and remove the cover.
Applies to: Vitodens 200-W B2HA 45, 60
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 22-23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.