Weil-McLain · Boiler troubleshooting
Multiple boiler control settings (general)
What is going on
Setup for multi-boiler systems is given in the control setting tables for each example. Required settings are listed there; other parameters can stay at factory default unless the job needs something different. Settings can be entered with the setup WIZARD or manually from the instructions in this manual. Set the outdoor reset ODT setpoint and the activate-contact-below-setpoint values to the design conditions of the system, or the system will not run correctly.
Check in this order
- Pick the example that matches the piping and zoning.
- Use the table for that example to set the TT inputs, outputs and priorities on each boiler.
- Set ODT setpoint and activate contact setpoints to the system design conditions.
- Use relays where an output is driven above 2.2 A or at a voltage other than 120 VAC.
Applies to: Multiple boiler installations, Evergreen Series 2 110/155/220/299/300/399
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Evergreen Series 2 advanced manual, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.