Weil-McLain · Boiler troubleshooting

Pre-troubleshooting checks and tools

CGi Series 5

What is going on

Basic checks before chasing any fault code on the boiler.

Check in this order

  1. Have a voltmeter that reads 120 VAC and 24 VAC, a microammeter (0-25 range), a continuity checker and a U-tube manometer.
  2. Confirm 120 VAC to the boiler (102 VAC minimum to 132 VAC maximum).
  3. Confirm the thermostat is calling for heat and its contacts, including zone controls, are closed. Check for 24 VAC between thermostat screw terminals and ground.
  4. Confirm wire connectors are fully plugged in at the control and the originating device.
  5. Confirm air pressure switch hoses are properly connected and undamaged.
  6. With the boiler off, check gas pressure upstream of the gas valve: 13 in. w.c. maximum for natural or propane.
  7. With the boiler on, check gas pressure upstream of the gas valve: 5 in. w.c. minimum natural, or 11 in. w.c. minimum propane.
  8. With the boiler on, check manifold pressure downstream of the gas valve against the manifold table.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 74. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.