Weil-McLain · Boiler troubleshooting
Pre-troubleshooting checks and tools
What is going on
Basic checks before chasing any fault code on the boiler.
Check in this order
- Have a voltmeter that reads 120 VAC and 24 VAC, a microammeter (0-25 range), a continuity checker and a U-tube manometer.
- Confirm 120 VAC to the boiler (102 VAC minimum to 132 VAC maximum).
- Confirm the thermostat is calling for heat and its contacts, including zone controls, are closed. Check for 24 VAC between thermostat screw terminals and ground.
- Confirm wire connectors are fully plugged in at the control and the originating device.
- Confirm air pressure switch hoses are properly connected and undamaged.
- With the boiler off, check gas pressure upstream of the gas valve: 13 in. w.c. maximum for natural or propane.
- With the boiler on, check gas pressure upstream of the gas valve: 5 in. w.c. minimum natural, or 11 in. w.c. minimum propane.
- With the boiler on, check manifold pressure downstream of the gas valve against the manifold table.
Applies to: CGi-25 to CGi-8
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 boiler manual, p. 74. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.