Viessmann · Boiler troubleshooting

System version 4: return temperature control with low loss header and three-way mixing valve

Vitotronic 100 GC1Vitotronic 300-K MW1S

What is going on

Vitorond 200 boiler with Vitotronic 100 GC1 on each boiler and one Vitotronic 300-K MW1S. The return temperature is controlled with a three-way mixing valve and a low loss header. Sensor T1 closes the mixing valve in proportion when the minimum return temperature is not reached, which protects the boiler. The sensor in the low loss header controls the supply temperature. Suited to older systems, systems where the hydraulics are not clearly defined, and systems where downstream heating circuits cannot be controlled.

Check in this order

  1. Code every Vitotronic 100 GC1 as shown in the system version 4 coding table.
  2. Size each boiler circuit pump so its flow is at least the maximum total heating circuit flow; recommended 110%.
  3. Check the connection diagram on site for completeness and function, because it is only a recommendation.
  4. Wire single-phase and three-phase pumps through field-supplied motor contactors or starters.

Applies to: System version 4, Vorond 200 with Vitotronic 100 GC1 and Vitotronic 300-K MW1S

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 16-17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.