Clean the heat exchanger and combustion chamber
What is going on
Cleaning requires a nylon brush and an FDA-approved liquid lime scale remover. Insulation contains ceramic fiber. Wear a NIOSH-certified N95 respirator, gloves and eye protection, and dampen the lining to limit dust.
Likely causes
- Scale or dirt in the combustion chamber
Check in this order
- Make sure power and gas are off, and let the boiler cool before draining water.
- Remove the silencer.
- Disconnect the gas pipe by unscrewing its two nuts. Remove the gas pipe.
- Remove the gas diaphragm if one is fitted.
- Disconnect the electrical connections to the electrodes, igniter and blower.
- Unscrew the four nuts on the burner door and remove the door.
- Check the back wall insulation and replace it if needed.
- Disconnect the condensate hose and siphon cap from the boiler.
- Clean the heat exchanger with the nylon brush and lime scale remover, then rinse.
Applies to: TRX150
More boiler guides
Related
NTI error codes · NTI parts · NTI tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NTI TRX150 manual, p. 90. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.