NTI · technician tips

NTI service menus, test modes and resets

20 tips for boiler: access codes, button combinations, test modes and the resets you need at the appliance.

Jump to: Access & passwords (1) · Service & test modes (8) · Reset & cancel (2) · Settings shortcuts (1) · Commissioning (8)

Access & passwords

Installer and service menu codes, and how to get into them.

Program module restore - login password

Boiler · Trinity Tft

Restoring non-safety settings from a program module (PIM) needs the password.

  1. Home - Configure - Display Setup - Program Module
  2. Touch Login and enter: sola
  3. Touch Restore Parameters and confirm Yes

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 15.0 Troubleshooting. Written in our own words; check the manual for your exact model.

Service & test modes

Forced fan, low and high fire, test and diagnostic modes, error history and live data.

Checking spark and gas valve voltage during ignition

Boiler · Trinity Tft

What to measure while the control is in its trial for ignition.

  1. Measure 120 VAC from J5-6 to ground for the spark generator
  2. Measure 24 VAC from J5-2 to J4-10 for the gas valve
  3. Look for the arc through the observation port next to the spark electrode in the burner door

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 15.0 Troubleshooting. Written in our own words; check the manual for your exact model.

Checking spark and gas valve voltage during ignition

Boiler · Trinity Tft

What to measure while the control is in its trial for ignition.

  1. Measure 120 VAC from J5-6 to ground for the spark generator
  2. Measure 24 VAC from J5-2 to J4-10 for the gas valve
  3. Look for the arc through the observation port next to the spark electrode in the burner door

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting. Written in our own words; check the manual for your exact model.

Reading the lockout and alert history

Boiler · Trinity Tft

The control keeps the 15 most recent lockouts and the 15 most recent alerts. Look there first whenever something seems off.

  1. On the Summary page touch the History button
  2. Read both the lockout log and the alert log before changing anything

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 15.0 Troubleshooting. Written in our own words; check the manual for your exact model.

Reading the lockout and alert history

Boiler · Trinity Tft

The control keeps the 15 most recent lockouts and the 15 most recent alerts. Look there first whenever something seems off.

  1. On the Summary page touch the History button
  2. Read both the lockout log and the alert log before changing anything

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting. Written in our own words; check the manual for your exact model.

Running a pump by hand

Boiler · Trinity Tft

Quick way to find out whether the control or the pump is at fault.

  1. Open the pump diagnostic page on the display
  2. Switch the pump on manually
  3. Measure for 120 VAC at the pump terminals on the line voltage strip

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 15.0 Troubleshooting. Written in our own words; check the manual for your exact model.

Running a pump by hand

Boiler · Trinity Tft

Quick way to find out whether the control or the pump is at fault.

  1. Open the pump diagnostic page on the display
  2. Switch the pump on manually
  3. Measure for 120 VAC at the pump terminals on the line voltage strip

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting. Written in our own words; check the manual for your exact model.

Turning the burner switch back on

Boiler · Trinity Tft

If the Summary page shows the burner switch off as the demand, the control is not allowed to fire.

  1. Open the Diagnostics pages
  2. Go to the burner test page and switch the burner on

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 15.0 Troubleshooting. Written in our own words; check the manual for your exact model.

Turning the burner switch back on

Boiler · Trinity Tft

If the Summary page shows the burner switch off as the demand, the control is not allowed to fire.

  1. Open the Diagnostics pages
  2. Go to the burner test page and switch the burner on

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting. Written in our own words; check the manual for your exact model.

Reset & cancel

Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.

Clearing the low water cutoff lockout after filling

Boiler · Trinity Tft

First-time fill or after the LWCO test.

  1. Fill the boiler so the amber LOW WATER light goes out
  2. Clear the lockout from the display board
  3. The burner should then fire

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 10.0 Boiler and Heating System Piping. Written in our own words; check the manual for your exact model.

Clearing the low water cutoff lockout after filling

Boiler · Trinity Tft

First-time fill or after the LWCO test.

  1. Fill the boiler so the amber LOW WATER light goes out
  2. Clear the lockout from the display board
  3. The burner should then fire

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 10.0 Boiler and Heating System Piping. Written in our own words; check the manual for your exact model.

Settings shortcuts

Where the useful parameters live and what they are set to from the factory.

Lead-lag cascade setup shortcuts

Boiler · Trinity Tft

Where the cascade settings live on the touchscreen.

  1. Give every boiler a different MB2 Modbus address under Configure - System Identification & Access
  2. On one boiler only set Master enable under Configure - Lead Lag Master Configuration
  3. Make the CH and DHW setpoints and outdoor reset changes on the master only
  4. On the boilers that run the CH and DHW pumps tick Use for Lead Lag Master demands under Pump Configuration

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 11.0 Lead Lag Instructions. Written in our own words; check the manual for your exact model.

Commissioning

Start-up and set-up steps that are easy to miss.

Combustion check procedure

Boiler · Trinity Tft

Set-up of CO2 and CO after start-up or propane conversion.

  1. Run the boiler at maximum fan speed and hold gas line pressure inside the allowed range
  2. Read CO2 and CO and adjust the throttle screw until both are inside the limits
  3. Drop to minimum fan speed and confirm combustion is still smooth and in range; if not, stop and call NTI

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 9.0 Gas Valve and Burner Set-Up. Written in our own words; check the manual for your exact model.

Combustion check procedure

Boiler · Trinity Tft

Set-up of CO2 and CO after start-up or propane conversion.

  1. Run the boiler at maximum fan speed and hold gas line pressure inside the allowed range
  2. Read CO2 and CO and adjust the throttle screw until both are inside the limits
  3. Drop to minimum fan speed and confirm combustion is still smooth and in range; if not, stop and call NTI

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 9.0 Gas Valve and Burner Set-Up. Written in our own words; check the manual for your exact model.

Dry run of the ignition sequence on new plastic vent

Boiler · Trinity Tft

Needed when the vent cement has had less than 8 hours to cure.

  1. With power off, glue the vent and air intake and keep the gas valve shut
  2. Pull the cable off the spark ignition transformer (keep 2 in from the spark circuit)
  3. Power up and make a heat call
  4. Let the control run three full ignition trials with pre-purge and post-purge until it locks out; repeat twice more for nine in total
  5. Power off and reconnect the spark cable

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 4.0 General Venting, Mandatory Pre-commissioning Procedure. Written in our own words; check the manual for your exact model.

Dry run of the ignition sequence on new plastic vent

Boiler · Trinity Tft

Needed when the vent cement has had less than 8 hours to cure.

  1. With power off, glue the vent and air intake and keep the gas valve shut
  2. Pull the cable off the spark ignition transformer (keep 2 in from the spark circuit)
  3. Power up and make a heat call
  4. Let the control run three full ignition trials with pre-purge and post-purge until it locks out; repeat twice more for nine in total
  5. Power off and reconnect the spark cable

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 4.0 General Venting, Mandatory Pre-commissioning Procedure. Written in our own words; check the manual for your exact model.

Flame failure check at commissioning

Boiler · Trinity Tft

Proves the flame safety is working after the first lights.

  1. Light the boiler at least three times in a row
  2. Unplug the single white flame probe wire (leave the orange spark cable alone - about 14,000 V)
  3. Let the boiler cycle: it makes 4 ignition cycles and then shows Hold 110
  4. Reconnect the flame wire, cycle power and confirm normal lighting

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 8.0 Lighting the Boiler. Written in our own words; check the manual for your exact model.

Flame failure check at commissioning

Boiler · Trinity Tft

Proves the flame safety is working after the first lights.

  1. Light the boiler at least three times in a row
  2. Unplug the single white flame probe wire (leave the orange spark cable alone - about 14,000 V)
  3. Let the boiler cycle: it makes 4 ignition cycles and then shows Hold 110
  4. Reconnect the flame wire, cycle power and confirm normal lighting

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 8.0 Lighting the Boiler. Written in our own words; check the manual for your exact model.

Low water cutoff test

Boiler · Trinity Tft

Check before leaving the job and each year.

  1. Before filling, power up: green POWER and amber LOW WATER lights should both be on and a burner demand should not fire, showing Lockout 67 ILK OFF
  2. Fill the boiler; the LOW WATER light goes out; clear the lockout and the burner fires
  3. With the burner running, press TEST: the LOW WATER light comes on and the burner shuts off with Lockout 67
  4. Once a year repeat the TEST step; every 5 years pull the cutoff and clean the wetted surfaces

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 10.0 Boiler and Heating System Piping. Written in our own words; check the manual for your exact model.

Low water cutoff test

Boiler · Trinity Tft

Check before leaving the job and each year.

  1. Before filling, power up: green POWER and amber LOW WATER lights should both be on and a burner demand should not fire, showing Lockout 67 ILK OFF
  2. Fill the boiler; the LOW WATER light goes out; clear the lockout and the burner fires
  3. With the burner running, press TEST: the LOW WATER light comes on and the burner shuts off with Lockout 67
  4. Once a year repeat the TEST step; every 5 years pull the cutoff and clean the wetted surfaces

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 10.0 Boiler and Heating System Piping. Written in our own words; check the manual for your exact model.

Same tips in your pocket

The HVACopedia app has these tips, every error code and the settings tables offline.

Open the app

For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.