NTI · Boiler troubleshooting

Blower not running

Trinity Tft

What is going on

No blower operation on a call for heat.

Likely causes

  • 5-position signal connector or 3-position power connector loose
  • Blown fuse A
  • Failed blower

Check in this order

  1. Verify the 3-position power Molex and the 5-position signal Molex are seated on the blower
  2. Check fuse A (it also feeds the spark generator and PUMP B)
  3. Measure voltage across pins 1 and 2 (black and white) of the 3-position connector; with 120 VAC present, pull the 5-position signal plug and the blower should spin at high speed - replace the blower if it does not

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 15.0 Troubleshooting. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.