Activate boiler as last in the boiler sequence

Vitotronic 100 GC1

What is going on

A dry contact on plug aVD makes this boiler the last one to fire in the sequence.

Check in this order

  1. Connect a dry contact to terminals 2 and 3 of plug aVD.
  2. Contact closed the boiler is activated as the last in the sequence and fires only if the other boilers cannot meet the load.
  3. Contact open the boiler returns to the current boiler sequence.

Applies to: Boiler sequence control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 51. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.