Viessmann · Boiler troubleshooting

Heating circuit pump economy shutdown

Vitocrossal 300 CA3B Dual Fuel

What is going on

The heating circuit pump is switched off and the supply set to 32°F (0°C) when one of the economy criteria is met.

Likely causes

  • Outdoor temperature above the value in coding a5.
  • Adjusted outdoor temperature above the value in coding a6.
  • Mixing valve has been trying to close for more than 12 min (coding a7).
  • Pump idle time from coding a9 has been reached.
  • Actual room temperature above the value in coding b5.

Check in this order

  1. Confirm there is no risk of frost before using the economy function.
  2. Set coding b0 in the Heating circuit group to 0.
  3. Note that switching to heating or raising the set room temperature restarts the pump early.

Applies to: Economy heating circuits on CA3B Dual Fuel

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 Dual Fuel Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.