Heating circuit pump economy shutdown
What is going on
The heating circuit pump is switched off and the supply set to 32°F (0°C) when one of the economy criteria is met.
Likely causes
- Outdoor temperature above the value in coding a5.
- Adjusted outdoor temperature above the value in coding a6.
- Mixing valve has been trying to close for more than 12 min (coding a7).
- Pump idle time from coding a9 has been reached.
- Actual room temperature above the value in coding b5.
Check in this order
- Confirm there is no risk of frost before using the economy function.
- Set coding b0 in the Heating circuit group to 0.
- Note that switching to heating or raising the set room temperature restarts the pump early.
Applies to: Economy heating circuits on CA3B Dual Fuel
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 Dual Fuel Service Instructions, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.