Viessmann · Boiler troubleshooting

Control calls for heat but the burner does not respond

Vitotronic 100

What is going on

The control is calling for heat but the burner stays off.

Likely causes

  • Burner is faulty and will not reset
  • Power venter has no separate 120 VAC supply to its motor
  • Air proving switch, blower wheel or timer/relay in the power venter is defective
  • Another accessory is defective

Check in this order

  1. Try to reset the burner with the reset button under the burner hood. Service the burner if needed and check the burner manual troubleshooting section.
  2. Make sure the power venter has its own 120 VAC supply to the motor. Check the power venter manual troubleshooting section.
  3. Check that all accessories work properly and replace any that do not. Use the accessory literature for guidance.
  4. If the F1 fuse has blown, replace it.

Applies to: Vitotronic 100 KW10B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 KW10B operating manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.