Weil-McLain · Boiler troubleshooting

Boiler will not fire with a flow switch or damper on J18

Weil-McLain ECO Tec Series 3

What is going on

The proof-of-closure circuit on J18 comes with a jumper. A flow switch or combustion air damper end switch can replace it, and the boiler only fires when that contact is closed.

Likely causes

  • Flow switch or damper end switch not closing
  • Contact not isolated (the circuit runs on 5 VDC)
  • Damper not driven because Input/Output 3 is not set up

Check in this order

  1. Safety first turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
  2. If nothing is wired there, the J18 jumper must be in place.
  3. The device must give an isolated contact; J18 carries 5 VDC. J18-1 has a PTC that trips at 340 mA (140 mA hold at 20°C).
  4. Flow switch no control settings needed.
  5. Damper assign Input 3 as AUX Pump/Output, mode local or System Damper. Output 3 then gives 120 VAC to the damper motor. Use a relay for other voltages or over 2.2 A.
  6. Multi-boiler system damper proof-of-closure inputs wired in series with the end devices. Local damper: wire each boiler's input on its own, not in series.

Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Field wiring J. Proof of closure, p.15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.