Fill boiler and hydrostatic pressure test

SVF 500/600 Series 1

What is going on

Install the test piping first. The relief valve must not be installed until the pressure test is done. Use pipe dope sparingly on all connections. Test pressure is 1.5 times the relief valve setting.

Check in this order

  1. Remove the relief valve if already installed.
  2. On the supply pipe, install two tees. Put the tee nearest the boiler vertical and install an NPT plug in it for the test. Put the second tee horizontal for the P/T gauge.
  3. Install a shut-off valve on the supply side and a drain valve plus shut-off valve on the return pipe.
  4. If testing above 160 psig, remove the automatic air vent in the cabinet on the heat exchanger port and replace it with a 1/2 in NPT plug.
  5. Open supply and return shut-off valves. Let water enter the bottom connection and let air exit the top until water reaches the top shut-off valve.
  6. Keep water flowing briefly to make sure all air is out of the heat exchanger.
  7. Close supply and return shut-off valves, then shut off water supply.
  8. Use the hand pump to raise pressure to 1.5 times the relief valve setting (see Table 4). Apply pressure gradually.
  9. Hold at test pressure for 10 minutes and keep gauge pressure constant.
  10. Check threaded joints for leaks and repair any found. If the heat exchanger leaks, contact a WM Technologies representative.
  11. Release pressure slowly and drain the boiler safely.
  12. Reinstall the automatic air vent if it was removed.

Applies to: SVF 500/600 boilers before relief valve installation

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, pp. 17-18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.