Viessmann · Boiler troubleshooting

Wire DHW, pool or spa demand to zone controller

Versatronik 10.WB1

What is going on

For multiple DHW, pool or spa demands, or an elevated boiler water temperature demand. The boiler pump connects to the Vitodens pump module, which sends a signal to the Versatronik. When the DHW aquastat or set-point control calls, its dry contact closes the DHW AQ input, which starts the DHW pump output and calls the zone controller.

Check in this order

  1. Remove power from the Versatronik 10.WB1 and the zone control.
  2. Remove the ZC/ZR jumper from the zone controller.
  3. Connect the L output of the Versatronik DHW heating pump output to the ZC terminal of the zone controller.
  4. Connect the potential-free (dry contact) output of the zone controller to the Versatronik DHW AQ input terminals.
  5. Power both devices and test operation.

Applies to: Versatronik 10.WB1 DHW, pool or spa pump control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 10.WB1 installation and operating manual, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.