Provide access to the boiler air inlet filter
What is going on
The boiler air inlet filter must stay reachable for periodic inspection and cleaning. Use an 8 in capped tee or route the air piping so it can be disconnected from the boiler air connection. Use only the air piping materials listed in the manual's approved materials figure.
Check in this order
- Install an 8 in capped tee on the air line, oriented so the cover is on the same side as the heat exchanger cleanout cover, or arrange the air piping so it disconnects easily.
- If using 6 in air piping, add a vent/air maker's reducer on top of the 8 in tee.
- Do not use a 6 in tee.
- Use only the approved air piping materials listed in the manual.
Applies to: Direct vent installations, sidewall and vertical
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 40, p. 42. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.