Viessmann · Boiler troubleshooting
System version 2: shunt pump for return temperature control
What is going on
Used where the distribution manifold is close to the boiler. The boiler water flow is reduced by the motorized isolation valve. T2 switches on the shunt pump when the minimum return temperature is not reached. If that is not enough, T1 must cut boiler water flow by at least 50% through the isolation valve or the heating circuit control units. If T1 cannot act on the isolation valves, it must regulate the downstream mixing valves instead.
Check in this order
- Size the shunt pump to about 30% of the total boiler throughput.
- Connect T2 to plug aJB and T1 to plug aJA, then set codings 4A and 4b to 1.
- Confirm the minimum return temperature is reached. If not, reduce boiler flow by at least 50% using T1.
- Set up the Vitocontrol-S coding per the table for system version 2.
- Verify the connection diagram on site, since it is a recommendation only.
- Use field-supplied motor contactors or starters for single-phase and three-phase pumps.
Applies to: Vitorond 200 VD2, system version 2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.