Viessmann · Boiler troubleshooting

CSD-1 field test of fixed high limit (where required by law)

Vitodens 222-F

What is going on

Field test procedure for the fixed high limit on Vitodens boilers. Viessmann is not responsible for damage caused by overheating during this test. A tripped fixed high limit gives a fault that needs a manual reset on the boiler control.

Check in this order

  1. Simulation 1 close the boiler valve and jumper across the flow switch.
  2. Simulation 1 run the boiler at high fire. It shuts down through the coding card (on B2TB models set coding address 06 to maximum) but the temperature should keep rising until the fixed high limit trips.
  3. Simulation 1 once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down.
  4. Simulation 2 throttle the boiler valve so the burner runs with as little flow as possible.
  5. Simulation 2 run the boiler to high fire using the relay test.
  6. Simulation 2 when the burner shuts down on the electronic limit, close the ball valve to stop the flow.
  7. Simulation 2 the temperature should keep rising until the fixed high limit trips. Then slowly open the boiler valve to cool the boiler down.
  8. Simulation 3 disconnect one of the wires on the limit switch. This creates a fault that requires a manual reset of the control.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 222-F, B2TB service instructions, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.