Weil-McLain · Boiler troubleshooting
Check call for heat and control inputs
What is going on
Use when the boiler does not start on a call for heat.
Likely causes
- Open thermostat or zone control contacts
- External limit open or not jumpered
- Loose or unseated control connectors
Check in this order
- Confirm heat demand is present and that thermostat and zone contacts are closed.
- Check for 24 VAC between thermostat wire nuts and ground.
- Make sure all external limit controls are installed and closed, or temporarily jumpered for testing.
- Confirm connectors are fully seated at the control module and at the originating control.
- Confirm gas pressure is within the limits on page 49 for natural gas or propane.
Applies to: SlimFit 550/750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SlimFit Series 3 boiler manual, p. 97. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.