Weil-McLain · Boiler troubleshooting
Choose direct connect or primary/secondary piping
What is going on
Primary/secondary is recommended and gives the most accurate system temperature. Direct connect is only for eligible heat-only systems.
Check in this order
- Check the system against the direct connect criteria first.
- Use primary/secondary piping if the system is ineligible or flow through the heat exchanger would be above the maximum.
- Place primary/secondary connection tees no more than 12 inches apart.
- Use a bypass pressure regulator on any system zoned with zone valves, unless a modulating circulator with dead-head protection is used.
- Do not replace the boiler circulator with anything other than the Taco 0015e3.
Applies to: Heating system piping
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 53, 54, 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.