Weil-McLain · Boiler troubleshooting

Choose direct connect or primary/secondary piping

ECO Tec Series 3

What is going on

Primary/secondary is recommended and gives the most accurate system temperature. Direct connect is only for eligible heat-only systems.

Check in this order

  1. Check the system against the direct connect criteria first.
  2. Use primary/secondary piping if the system is ineligible or flow through the heat exchanger would be above the maximum.
  3. Place primary/secondary connection tees no more than 12 inches apart.
  4. Use a bypass pressure regulator on any system zoned with zone valves, unless a modulating circulator with dead-head protection is used.
  5. Do not replace the boiler circulator with anything other than the Taco 0015e3.

Applies to: Heating system piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 53, 54, 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.