Weil-McLain · Boiler troubleshooting
Prevent combustion air contamination
What is going on
Chlorine or fluorine products in the boiler air supply form acid in the boiler and can eat through the heat exchanger. Check the intake area before you accept the install or service.
Likely causes
- Spray cans with chloro/fluorocarbons, chlorine bleaches, detergents or solvents, or chlorinated cleaners near the air inlet
- Pool, laundry, dry cleaning, beauty salon, auto body or similar areas feeding the air inlet
- Refrigerant leaks, hydrochloric/muriatic acid, cements, glues or paint removers nearby
Check in this order
- Do not operate an Ultra boiler whose combustion air inlet is in a laundry room or pool area.
- Remove any listed contaminating products from the boiler room or the air inlet area.
- If products cannot be removed, have the installer re-pipe the combustion air and vent to an uncontaminated location.
- If contaminants were present for a long time, have a technician inspect the boiler for acid corrosion.
Applies to: Ultra Series 4 gas-fired water boilers, combustion air inlet and boiler room
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 user's information manual, p. 4. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.