Remove and inspect the burner

SVF Series 1

What is going on

Burner access for cleaning or replacement. Ceramic fiber materials are present; follow the handling precautions in the manual.

Check in this order

  1. Shut off power to the boiler.
  2. Close the external manual gas valve.
  3. Let the boiler cool to room temperature.
  4. Remove the top rear and middle panels.
  5. Remove the eight M6 nuts on the burner access plate with an 11 mm socket.
  6. Lift the access plate straight up by the handle and set it aside.
  7. Inspect the access plate gasket and replace if damaged.
  8. Remove the eight M6 nuts holding the burner.
  9. Lift the burner by hand using the inside baffles. Do not drag the fiber mesh.
  10. Inspect the graphite burner gasket and replace if damaged.
  11. Check burner flame and combustion after reassembly (page 88).

Applies to: SVF 1500-3000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 96. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.