Install valve actuator adaptor and wire valve
What is going on
Fit the 120 V or 24 V valve adaptor and connect the actuator.
Check in this order
- Disconnect power to the control.
- Mount the 120 V or 24 V valve adaptor on the DIN rail inside the connection enclosure.
- Insert plug gS into socket gS on the control.
- Secure the cable with a tie.
- Connect the adaptor black wire to terminal 8, 9 or 10 on connection aBH.
- Connect the valve actuator wires to the adaptor terminals as shown in the figures.
- Set the operating time via coding address 40 (5 to 199 s).
Applies to: Boiler return mixing or isolation/modulating valve actuator (VD2/VD2A/CT3)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 installation and service instructions, p. 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.