Viessmann · Boiler troubleshooting

Burner control via eBUS does not respond

Versatronik 200

What is going on

The controller communicates with the burner control unit (FA) over eBUS, connected at the FA eBUS terminals. The controller sends a heat request and the burner control returns data and status.

Likely causes

  • Burner control unit not sending a valid eBUS message
  • eBUS supply not active when the burner does not supply the bus

Check in this order

  1. Confirm the burner control unit (FA) is transmitting a valid eBUS message.
  2. If the burner does not supply the bus, activate the eBUS supply in Expert level / System.
  3. Use the test function to check operation with and without eBUS supply.

Applies to: Versatronik 200 with eBUS burner control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 Installation and Operating Manual, p. 155. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.