Viessmann · Boiler troubleshooting
Installing a 3-way mixing valve actuator adaptor
What is going on
Install a 120V or 24V valve adaptor on the DIN rail inside the connection enclosure, then wire the actuator through it. The actuator runtime is set with coding addresses.
Check in this order
- Disconnect power to the control.
- Install the 120V or 24V valve adaptor on the DIN rail in the connection enclosure.
- Insert plug gS into socket gS on the Vitotronic.
- Fasten the cable with a tie.
- Connect the adaptor's black wire to terminal 8, 9 or 10 on the DIN rail.
- Connect the valve actuator wires to the adaptor terminals.
Applies to: 3-way mixing valve actuator (A1, M2, M3)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Installation and Service, p. 19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.