Viessmann · Boiler troubleshooting

Annual heating contractor service checklist

Vitorond 200 VD2A

What is going on

Annual service must be done by qualified personnel. Correct any deficiencies right away.

Check in this order

  1. Test safety high limits by lowering settings and switching the burner on and off.
  2. Test burner and accessories against their maintenance checklist.
  3. Test and establish proper system water chemistry.
  4. Check flue pipe, chimney connection and chimney.
  5. Check the pressure relief valve, system pressure and automatic feed if fitted.
  6. Check heating pipe joints, valves and air vents for leaks and correct any leaks at once.
  7. Check combustion air and ventilation to the boiler room.
  8. Check for combustibles or chemicals stored near the boiler.
  9. Test the low water cut-off and confirm it works per the manufacturer.
  10. Check oil-tight fuel lines and replace or clean fuel filters annually.
  11. Check and inspect the oil tank.
  12. Check gas-tight connections on gas piping, unions, gas valve and manifold.
  13. Check proper ignition on oil or gas operation.
  14. Have a qualified technician perform the combustion test.
  15. Test the door safety switch.
  16. Check the low- and/or high-pressure gas switch if fitted.
  17. Inspect the main burner flame.
  18. Check the circulating pump lubrication or maintenance if field-installed.

Applies to: Vitorond 200 VD2A boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2A service instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.