Viessmann · Boiler troubleshooting

Burner adjustment and CO check

Vitocrossal 300 CA3B Dual Fuel

What is going on

Carbon monoxide build-up from incorrect burner adjustment is a serious health risk. A CO test is required before and after any work on the gas appliance. Adjustment is checked with the boiler at operating temperature.

Check in this order

  1. Take a CO test before starting work.
  2. Heat the boiler to operating temperature (minimum 40°C / 104°F).
  3. Check the burner adjustment at full load and also in the partial load range.
  4. Take a CO test again after the work is finished.
  5. Check the heating water side connections for leaks about every 500 operating hours.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.