Example D - heat exchanger shell-side and heating circuit requirements
What is going on
Heat exchanger shell-side and tube-side piping, pumps and sizing must come from the heat exchanger manufacturer. Tube-side flow and temperatures must meet the heating system. The shell-side circuit needs its own expansion tank. The heating system circuit needs its own expansion tank and its own relief valve, sized to protect the system and the heat exchanger piping.
Check in this order
- Get shell-side and tube-side piping and pump requirements from the heat exchanger manufacturer.
- Confirm tube-side flow and temperature meet the heating system needs.
- Size the heat exchanger with the manufacturer.
- Install a separate expansion tank on the shell-side circuit.
- Install a separate expansion tank and relief valve on the heating system circuit.
Applies to: Example D multiple boiler piping with heat exchanger
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Evergreen Series 2 advanced manual, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.