Beckett · Boiler troubleshooting

Priming the CF375 oil pump (air in the oil line)

Beckett CF375

What is going on

How to bleed the fuel unit on the CF375 with the GeniSys 7565 control.

Likely causes

  • Air in the supply line after a run-out, filter change or new install

Check in this order

  1. Never let oil spray into a hot chamber while bleeding. Put a gauge on the nozzle port line or open the bleed valve fully so oil does not collect in the chamber.
  2. Do not start the burner if the chamber is flooded with oil, full of vapour or very hot. Flooded = power and oil off, clean out the oil first.
  3. Open the oil valves, close the air band and crack the air shutter (starting point only).
  4. Call for heat. Open the bleed fitting into a container until all bubbles and froth are gone, then close it.
  5. For a long purge while the igniter is still on, tap the ACTION button. Pump Prime mode runs motor, igniter and valve for 4 minutes with the SYS light solid yellow, then SYS goes green and the control returns to standby.
  6. Other way per the manual after the burner starts, hold ACTION about 15 seconds until SYS turns yellow, then let go.
  7. Set pump pressure to the boiler maker's value (factory nozzle port setting is 140 psig or more).
  8. Do not try to relight with the burner running if the flame goes out during start-up.

Applies to: Beckett CF375 with GeniSys 7565 control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Beckett CF375 Burner Manual (Weil-McLain WGO/WTGO/SGO sizes 8-9, 0125), Start up burner/set combustion, p.13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.