Beckett · Boiler troubleshooting

Setting CF375 combustion with instruments

Beckett CF375

What is going on

Use an analyzer, not your eyes. Run the burner 5-10 minutes first.

Likely causes

  • Wrong air setting
  • Wrong draft
  • Biodiesel blend reading off on the analyzer

Check in this order

  1. Set over-fire draft to the boiler maker's number (natural draft is usually -0.01 to -0.02 in. w.c.).
  2. Adjust the air until you get a trace of smoke. Note the CO2 (or O2) there.
  3. Add air to drop CO2 by 1.5 to 2 points (O2 goes up about 2.0 to 2.7 points). Example from the manual: 13.5% to 11.5% CO2.
  4. Smoke should now be zero. If draft changed, recheck smoke and CO2.
  5. Tighten the air band, shutter and head plate screws. If the burner has a cover, recheck with the cover on.
  6. Biodiesel set the analyzer to light / #2 oil. On B100 the CO2 reads about 0.3% low, so add 0.3%. Easier: use O2, aim for 4.5-5.7% O2 (about 11.3-12.3% CO2).
  7. Start and stop several times and test the primary control and all safety controls.

Applies to: Beckett CF375

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Beckett CF375 Burner Manual (Weil-McLain WGO/WTGO/SGO sizes 8-9, 0125), Set combustion with instruments, p.14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.