Viessmann · Boiler troubleshooting
Mount the CombiPLUS on the wall
What is going on
Use the supplied template and hardware, and set the position to match the flex pipe length in use.
Check in this order
- Pull the bottom of the boiler about 1/2 in (12 mm) from the wall and slide the mounting template between the wall and the boiler. Release the boiler so its weight holds the template.
- Use the upper outline for 12 in flex pipe, or the lower outline for 7 in flex pipe.
- Drill the two top mounting holes and the two holes in the centre of the slots. Remove the template.
- Install wall anchors if required, then fit the lag bolts with washers through the wall anchors and the CombiPLUS slots.
- Leave the lag bolts loose enough to allow up and down adjustment in the slot.
Applies to: CombiPLUS A mounting on Vitodens 100-W WB1B
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W WB1B installation and service instructions, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.