Viessmann · Boiler troubleshooting
Fill the heating system with water
What is going on
Flush the system before filling to avoid sludge settling in the boiler. Antifreeze may be used where freezing is possible.
Check in this order
- Flush the system piping to remove debris and sludge.
- Fill the system at the boiler fill connection (BF) and bleed air fully from the boiler drain (BD).
- Set the system fill pressure about 3 psig above the cold static head.
- Open the system isolation valves at C and D if installed.
- Check the expansion tank precharge. If it is below system static pressure, inflate the membrane to slightly exceed system pressure.
- Confirm the system fill pressure equals the expansion tank pressure at about 60°F (15.6°C).
- Use water treatment where feed water has high mineral content or hardness.
- If using antifreeze, use only hot water heating antifreeze at 40% for protection to -10°F (-23°C). Do not use automotive silicate-based antifreeze.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.