Weil-McLain · Boiler troubleshooting

Switching a Weil-McLain oil boiler to B100 biodiesel

Weil-McLain WGO/WTGO/SGOWeil-McLain Ultra Oil

What is going on

Notes from the Weil-McLain B100 addendum for Ultra Oil, WGO, WTGO and SGO boilers.

Likely causes

  • Poor cold-weather fuel flow with high blends
  • Filter plugging from loosened tank sludge
  • Wrong firing rate after the switch

Check in this order

  1. Only UL-approved B100 burners may burn B100. The addendum lists the B100 burner part number for each boiler size.
  2. Standard #2 oil in Canada (CAN/CGSB-3.2) allows only up to 5% biodiesel. Think about cold-weather fuel properties before going higher.
  3. Use one-pipe with an oil deaerator and 10 micron filtration. Expect more filter changes early on.
  4. Before switching, set the burner at 12.25-12.5% CO2 on #2 oil.
  5. Once on B100, drop pump pressure 6-8 psi to keep the same GPH as #2 oil.
  6. Use the addendum tables (Beckett and Carlin, #2-B20 vs #2-B100 columns) for nozzle, pump pressure and air settings.

Applies to: Weil-McLain Ultra Oil (UO-3 to UO-5) and WGO/WTGO/SGO (GO-2 to GO-9) oil boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Oil/WGO/WTGO/SGO B100 Biofuel Addendum and Burner Cross Reference Guide 550-143-077/1224, p.1-2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.