Weil-McLain · Boiler troubleshooting
Check blower speeds at low, medium and high fire
What is going on
Compare blower RPM at each firing rate against the reference table. Altitude setting affects this check.
Likely causes
- Blower speed out of range
- Incorrect altitude setting
Check in this order
- For installs above 5,500 ft, set the high altitude option in the boiler setup menu. The control adjusts low fire and ignition rates automatically.
- For installs below 5,500 ft, do not enable high altitude.
- Go to Manual Test Mode on the control display.
- Set firing rate to Low. Write down the RPM and compare with the table in Figure 74 on page 82. Low fire rate is adjusted in the boiler setup menu.
- Set firing rate to MEDIUM (ignition rate). Write down RPM. It should be within 200 RPM of the table value.
- Set firing rate to High. Write down RPM. It should be within 200 RPM of the table value.
- If any value is outside these ranges, contact the factory for technical assistance.
Applies to: SlimFit 1000-2000 MBH Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 92. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.