Direct vent sidewall termination (vent and air)

SlimFit Series 2

What is going on

Direct vent uses separate vent and air pipes through the sidewall. Vent and air pipe materials must be from Figure 22. Each pipe needs its own penetration and termination elbow. Exposed pipe above 4 ft needs an insulated enclosure.

Likely causes

  • Flue gas leakage or component damage if vent and air piping are combined
  • Freezing of condensate in exposed vent pipe if the outside run is too long

Check in this order

  1. Install the vent manufacturer's SlimFit Vent Adapter at the boiler vent outlet and a reducer if needed.
  2. Cut the air pipe hole sized per the vent/air pipe manufacturer.
  3. Cut the vent pipe hole. For combustible construction, make it at least 3/8 in larger than the vent pipe diameter.
  4. Install a corrosion-resistant metal thimble in the vent hole and isolate the pipe per local code.
  5. Install stop plates from the vent pipe manufacturer for both vent and air pipes, with holes just larger than each pipe.
  6. Insert the vent and air pipes from outside until the female shoulders rest against the outer stop plates.
  7. Install an outward-facing 90-degree elbow on the vent termination and a down-turned 90-degree elbow on the air termination.
  8. Run exposed vent and air pipes up to 4 ft with no enclosure, secured with braces no more than 24 in apart.
  9. If external venting goes beyond 4 ft, install an insulated enclosure and bring the terminations out through it.
  10. Install bird screens in the open ends of both elbows.
  11. Seal exterior openings thoroughly with exterior caulk.
  12. Keep the required clearances in Figures 27 and 36 for multiple terminations.

Applies to: SlimFit 1000-2000 Series 2 direct vent, sidewall

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit-1000-2000 Boiler Manual 550-100-561/1225, p. 39-40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.