Viessmann · Boiler troubleshooting
Remove front enclosure panel and fill condensate trap
What is going on
Required before some service steps. Gas must be shut off first. The condensate trap is filled with water before the first start.
Check in this order
- Close the main gas supply valve.
- Remove the external accessories connection box cover.
- Loosen the bottom screws without removing them completely.
- Slide out and remove the front enclosure panel.
- Remove the retaining clip from the condensate trap and set it aside.
- Disconnect the condensate trap and fill it with water.
- Reinstall the condensate trap and secure it with the retaining clip.
Applies to: Vitodens 200-W B2HB boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Service Instructions, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.