Viessmann · Boiler troubleshooting

Return temperature control with shunt pump and return valve

Vitotronic 300 GW2

What is going on

Used where the distributor is close to the boiler and boiler water flow must be reduced.

Check in this order

  1. When the return temperature drops below the required minimum, sensor T2 switches on the shunt pump.
  2. If the minimum return temperature is still not reached, sensor T1 proportionally closes the return valve.
  3. Check that the minimum return temperature is held after the valve closes.

Applies to: System type 2 with Vitorond 200 VD2 and modulating burner

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.