Viessmann · Boiler troubleshooting
Set LON participant number and update LON participant list
What is going on
Used when the Vitotronic 300 GW2 is connected in a LON BUS system with Vitotronic 200-H. The LON communication module must be fitted first.
Likely causes
- The same LON participant number is assigned twice in the LON BUS system.
Check in this order
- Fit the LON communication module (accessory).
- Set the LON participant number in coding 1, address 77. Factory setting is 77: 1.
- Make sure every participant has a different number.
- Make sure the control unit is coded as fault manager (coding 79: 1) and all participants are connected.
- Press the w and OK buttons together for about 2 seconds.
- Press the D button to start the participant check.
- Wait about 2 minutes for the participant list to update.
Applies to: Vitotronic 300 GW2 with Vitotronic 200-H and Vitocom 300 on LON
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW2 installation and service instructions, p. 66. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.