Navien · Boiler troubleshooting

Indoor vent termination clearances

NCB700

What is going on

Clearances for two-pipe, concentric and low-profile indoor venting. The exhaust and intake terminations must stay apart, and concentric sidewall terminations must not be stacked.

Check in this order

  1. Keep at least 12 in (300 mm) between the intake and exhaust terminations for non-concentric sidewall and vertical venting.
  2. Keep the intake and exhaust at least 12 in (300 mm) from any obstruction above, below, left or right.
  3. Keep the termination at least 12 in (300 mm) above the highest expected snow level or grade, or as local code requires, whichever is greater.
  4. For concentric vertical venting, do not go above 24 in above the roof.
  5. For cascade installs, keep 12 in horizontal clearance between terminations for both sidewall and vertical venting.
  6. Do not vertically stack concentric terminations on sidewalls. Exhaust recirculation will cause bad boiler operation.
  7. For twin-pipe terminations, use only the allowed orientations. Never put the exhaust nearest the ground.

Applies to: Indoor boiler installs, sidewall and vertical venting

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 73-75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.