Indoor vent termination clearances
What is going on
Clearances for two-pipe, concentric and low-profile indoor venting. The exhaust and intake terminations must stay apart, and concentric sidewall terminations must not be stacked.
Check in this order
- Keep at least 12 in (300 mm) between the intake and exhaust terminations for non-concentric sidewall and vertical venting.
- Keep the intake and exhaust at least 12 in (300 mm) from any obstruction above, below, left or right.
- Keep the termination at least 12 in (300 mm) above the highest expected snow level or grade, or as local code requires, whichever is greater.
- For concentric vertical venting, do not go above 24 in above the roof.
- For cascade installs, keep 12 in horizontal clearance between terminations for both sidewall and vertical venting.
- Do not vertically stack concentric terminations on sidewalls. Exhaust recirculation will cause bad boiler operation.
- For twin-pipe terminations, use only the allowed orientations. Never put the exhaust nearest the ground.
Applies to: Indoor boiler installs, sidewall and vertical venting
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 73-75. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.