Wiring DHW recirculation with 24 VAC powered thermostats
What is going on
Same DHW recirculation options as the dry-contact layout, with 24 VAC powered thermostat and aquastat inputs.
Check in this order
- Connect thermostat and aquastat inputs to their 24 VAC neutral and line terminals.
- Connect the recirculation pump (max 2.5 A) with line and neutral.
- Select the recirculation mode in the DHW Recirculation menu, following the same options as the dry-contact layout.
Applies to: NCB700 boilers with zone pumps and DHW recirculation
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 212. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.