External boiler activation contact (isolation valve open/closed)
What is going on
Dry contact at plug aVH controls boiler activation. Essential on multi-boiler systems. Lead boiler contact must stay closed.
Check in this order
- Connect a dry contact to terminals 2 and 3 of plug aVH.
- Contact closed preheat for follow-up boilers runs first (coding 2b). Then minimum temperature is held and burner stages can be switched externally. Setpoint is chosen with coding 9b.
- Contact open isolation valve closes after about 5 minutes (coding 2C). No external burner override and no minimum temperature is held.
Applies to: VD2/VD2A/CT3/CM2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100, GC1 installation manual, p. 60. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.