Weil-McLain · Boiler troubleshooting

Boiler will not start - startup checks

SVF 500/600 Series 1

What is going on

Work through these checks in order before going to the troubleshooting section.

Likely causes

  • Loose connection or blown fuse
  • Service switch off
  • Gas off at meter or boiler
  • Control settings wrong for application
  • Warm weather shutdown active
  • Thermostats set below room temperature
  • External limit controls open
  • Boiler water above 200°F
  • Closure switch contacts open
  • Incoming gas pressure outside min/max on page 63

Check in this order

  1. Check for loose connections, a blown fuse, or a service switch in the off position.
  2. Confirm gas is on at the meter and at the boiler.
  3. Confirm control settings match the application.
  4. Confirm the warm weather shutdown is not active.
  5. Confirm thermostats are set above room temperature.
  6. Confirm external limit controls are closed (if used) and boiler water is below 200°F.
  7. Confirm closure switch contacts are closed.
  8. Confirm incoming gas pressure is within the minimum and maximum on page 63.
  9. If the issue remains, go to the Troubleshooting section starting on page 119.

Applies to: SVF 500/600 Series 1 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 Boiler Manual, p. 98. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.