Weil-McLain · Boiler troubleshooting
Boiler will not start - startup checks
What is going on
Work through these checks in order before going to the troubleshooting section.
Likely causes
- Loose connection or blown fuse
- Service switch off
- Gas off at meter or boiler
- Control settings wrong for application
- Warm weather shutdown active
- Thermostats set below room temperature
- External limit controls open
- Boiler water above 200°F
- Closure switch contacts open
- Incoming gas pressure outside min/max on page 63
Check in this order
- Check for loose connections, a blown fuse, or a service switch in the off position.
- Confirm gas is on at the meter and at the boiler.
- Confirm control settings match the application.
- Confirm the warm weather shutdown is not active.
- Confirm thermostats are set above room temperature.
- Confirm external limit controls are closed (if used) and boiler water is below 200°F.
- Confirm closure switch contacts are closed.
- Confirm incoming gas pressure is within the minimum and maximum on page 63.
- If the issue remains, go to the Troubleshooting section starting on page 119.
Applies to: SVF 500/600 Series 1 boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 98. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.