Surging water line or water carried into the steam mains

Weil-McLain SGO Series 4

What is going on

Water level jumps around in the gauge glass, or water is pushed into the steam mains (priming).

Likely causes

  • Oil, dirt or other impurities in the boiler water (new boiler not skimmed)
  • Water line set too high
  • Piping not as shown in the manual
  • Zone valves opening fast and dropping steam pressure suddenly

Check in this order

  1. Skim the boiler run 1-1/2 in. pipe from the skim tapping to a drain with a tee to see the water level, and raise the water to the middle of the skim tapping.
  2. Fire the burner just enough to keep the water hot but not steaming. Keep feeding water and cycle the burner so pressure does not build. Keep going until the discharge runs clear.
  3. Drain the boiler while it is warm, not hot. Remove the skim piping, close the drain and refill with fresh water to the normal water line.
  4. Fire and steam for about 15 minutes to drive off dissolved gases, then stop.
  5. Only skim the boiler. Do not try to clean old system piping, it can start leaks.
  6. If the water line is too high, set it back to the normal height.
  7. Check the piping against the manual drawings.
  8. With zone valves, slow the valve opening time or use slow-opening valves.

Applies to: SGO-3 to SGO-9 oil-fired steam boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Troubleshooting p.7; Skim steam boiler p.34. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.