Viessmann · Boiler troubleshooting
Low water cut-off and water connections
What is going on
A low water cut-off may be required by local codes. If the boiler is above radiation level, an approved low water cut-off must be installed in all cases, supplied by the heating contractor. Boilers work in any fully pumped hot water system. Minimum system pressure is 14 psig.
Check in this order
- Install an approved low water cut-off if the boiler sits above radiation level.
- Do not put an isolation valve between the boiler and the low water cut-off.
- Keep system pressure at 14 psig minimum.
Applies to: Vitocrossal 300 CU3A
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A application guide, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.